current monitoring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Response Time 1 sec.
Accuracy ±2% of full scale
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
LCD Backlight O at low currents; illuminates when monitored current exceeds 4.5A;
ashes during an alarm state while current remains above 4.5A
On-State Resistance ≤1.0 Ω
O-State Resistance 1.0 MΩ
Setpoint Target Range, Switch Setting A* ±40% of learned nominal current; max. learned current of 142A to enable an upper trip limit at or below 200A
Setpoint Target Range, Switch Setting B* ±60% of learned nominal current;max. learned current of 125A to enable an upper trip limit at or below 200A
Switch Setting C* On/O Status; contacts are closed while amperage is above 2.5A
Alarm Reset Range ±5% of learned nominal current **
Setpoint Calibration Learn Period 30 sec.; self-learning, pushbutton reset
Normal-to-Alarm Output Delay 1 sec. maximum
Alarm-to-Normal Output Delay 30 sec. nominal
Insulation Class 600VAC RMS (UL); 300VAC RMS (CE)
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2
* Trip point switch positions A and B are not for use in applications where the current will uctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will uctuate by more than 60%, use the H11D for on/
o status (position C) only.
** The upper trip limit alarm resets when the current drops by 5% of the learned nominal current limit. The lower trip limit alarm resets when the current rises by 5% of learned nominal current limit.
Specication Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001.
The product design provides for basic insulation only.
Do not use the LCD as evidence of applied voltage.
DESCRIPTION
The Hawkeye TruStat H11D is a microprocessor based, self-learning, self-calibrating
current switch. It is designed for user ease, providing calibration-free status for
both under and overcurrent, an LCD display, and slide-switch selectable trip point
limits. At initial power-up, the H11D automatically learns the average current on the
line with no action required by the installer. Once a current is learned, the switch
monitors for changes in current greater than the selected range.
APPLICATIONS
HVAC fans, pumps, and blowers
Monitoring status of industrial process equipment
FEATURES
Backlit LCD display...view the monitored current (up to 200A)...eliminates the
need for expensive handheld meters and oers easy visibility in dark enclosures
Automatic calibration...reduced errors and installation costs
Slide-switch selectable trip point limits...application versatility
Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
Records and displays the amperage level that trips the alarm...simplies
troubleshooting
Reset function can be used when unpowered...reduces the possibility of an
undesirable arc ash incident
Monitors current for both under- and over-load in one package
100% solid state...no moving parts to fail
Small size ts easily inside small starter enclosures...saves space
Self-gripping iris for easy installation
Bracket can be installed in three dierent congurations...added exibility
5-year warranty
LCD Display
Current Switch:
Auto Calibration,
Automation Systems
Maximize Reliability
Minimize Installed Cost
Year
Warranty
5
H11D
H11D
TM
LCD
DISPLAY!
LCD
DISPLAY!
HQ0003679.C 01131
Przeglądanie stron 0
1 2

Podsumowanie treści

Strona 1 - Automation Systems

current monitoringVERIS INDUSTRIES800.354.8556+1 503.598.4564www.veris.comSPECIFICATIONSSensor Power Induced from monitored conductorResponse Time 1

Strona 2 - ACCESSORIES

current monitoring800.354.8556+1 503.598.4564www.veris.comDIMENSIONAL DRAWINGAPPLICATION/WIRING DIAGRAMFUNCTIONAL ILLUSTRATIONFan or Pump CONTROLLERDi

Komentarze do niniejszej Instrukcji

Brak uwag